The Domain

  • Applicable in automation systems of 115U, 135U/155U and 150U of the Simatic S5
  • Compatible with CPU 416 with RS 7 Software
  • Compatible with CPU 945 (941, 942, 943, 944) or CPU 948 (946/947, 928) with RS 5 Software
  • Synchronous mode: S7 and S5 Program run concurrently (Particularly suitable for extensions of present plants
  • IT function (Email Client, Webserver, FTP)
  • Upgrade your S5 PLC to an S7 PLC in a Flash


Technical Details

Serial Interfaces:
1 x AS511 (TTY) or
RS232 with 15pin D-sub female,
1 x RS232 with 9pin D-sub male
Ethernet-Interfaces:
10 / 100 Mbps
2 x TP (RJ45)
(2- port Switch)
Interfaces optional: Keyboard and mouse via PS2
via PC-MIP:
4 x RS232
4 x RS422 / 485
graphics 1.280 x 1.024
Transport Protocols:
TCP/IP,
ISO on TCP (RFC1006)
Serial Protocols: 3964(R), RK512, ASCII, STX/ETX
RAM Extension: 64 MB SDRAM,
128 KB Bios Flash,
2 MB retained SRAM
Mass storage: Compact Flash 1 socket
for CF cards or microdrives
Power Supply: 5 V +/- 5% @5A
Dimensions [in mm]: Height: 6 HE
Width: 8 TE


Order Number

Height: 6 HE
Width: 8 TE
700-4300-01
X5 / X7 CPU for
AG 135U/155U
700-4310-01
X5 / X7 CPU for
AG 150U
700-4320-01
RS 5 Software,
compatible with CPU 945
700-4330-01
RS 5 Software,
compatible with CPU 948
700-4331-01
RS 7 Software, compatible with CPU 416/945
(synchronous mode)
700-4340-01
RS 7 Software, compatible with CPU 416/948
(synchronous mode)
700-4341-01

Including serial parameterization cable
Note: The software can only be used in combination with a
X CPU hardware. For each X CPU one software module can be ordered. Please specify the order number of the RS Software with your X CPU order.


Accessories

  • PC MIP module, graphics, 1.280 x 1.024
  • PC MIP Extension Board
  • Serial parameterization cable
  • PC MIP module, 4 x RS422 / 485
  • PC MIP module, 4 x RS232


What is SYNCRHONOUS MODE?

  • The X CPU with RS 7 Software supports the so-called synchronous mode.
  • This means that besides the S7 functions, the complete S5 functions are contained in the CPU.
  • The existing S5 program is completely executable.
  • Blocks from the S5 program do not have to be re-edited. They can be called in the S7 program.


S5 program and S7 program run simultaneously!

ADVANTAGES:
  • Step 5 blocks that can only be ported to S7 with high complexity, remain in Step 5 and are called from the Step 7 operating system.
  • Access to external periphery, where blocks are only available in Step 5.
  • Existing S5 hardware and S5 programs can be integrated into systems, that do not support S5 components (e.g. Simatic PC S7)
  • Time-consuming and cost-intensive converting of programs is not applicable.



IN THE PAST TO UPGRADE S5 TO S7
  • Purchasing new hardware
  • Conversion of Programs
  • Time-consuming, cost-intensive



UPGRADE TODAY
  • Hardware remains constant (exception: CPUs)
  • S5 Program remains constant
  • S7 Program and S5 Program run concurrently
  • Time-saving, cost-effective